XLPE Insulated Fireproof / Flame Retardant Cables And Wires IEC60502
Application:
It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower.
It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.
0.6/1*3.6/6kv,6/6kV,6/10kV,8.7/10kV, 8.7/15kV,12/20kv, 21/35kV, 26/35kV.GB/T12706-2002 standard(The same as IEC60502).power cable
Type |
Description |
Main Application |
|
Cu core |
Al core |
||
(ZR)YJV or (ZR)YJY |
(ZR)YJLV or (ZR)YJLY23 |
(Flame retardant) Cu, Al core XLPE insulated, PVC or PE sheathed power cable. |
For laying indoor, tunnel, underground and canal. Unable to bear external mechanical pulling force and pressure during laid. |
(ZR)YJV22 or (ZR)YJY23 |
(ZR)YJLV22 or (ZR)YJLV23 |
(Flame retardant) Cu, Al core XLPE insulated, steel armoured, PVC or PE sheathed power cable. |
For laying indoor, tunnel, underground and canal. Able to bear external mechanical pulling force , but unable to bear large pulling force. |
(ZR)YJLV32 or (ZR)YJLV33 |
(ZR)YJLV32 or (ZR)YJLV33 |
(Flame retardant) Cu, Al core XLPE insulated, fine steel wire armoured, PVC or PE sheathed power cable |
For laying in shaft, water under ground and large difference of level, able to bear mechanical pressure and moderate pulling force. |
(ZR)YJLV42 or (ZR)YJLV43 |
(ZR)YJLV42 or (ZR)YJLV43 |
(Flame retardant) Cu, Al core XLPE insulated, thick steel wire armoured, PVC or PE sheathed power cable |
For laying in the water, seabed and large difference of level, able to bear large mechanical pressure and pulling force. |
Using Features:
1. Rated voltage: Uo/U: 26/35kV, 21/35kV, 12/20 kV (24 kV), 8.7/10kV, 8.7/15kV, 6/6kV, 6/10kV.
2. No. of core: Single-core, Three-core.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. Long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250.
4. D.C Resistance of the conductor complies with the stipulations of GB/T3956-1997.
5. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.